3601h Digital Output Control

This object shall permit controlling of digital output values over fieldbus. Two sub-indexes are bit-masked values where the bit offset corresponds to the digital output id starting with bit offset 0 = DOUT1.

Sub-index 1 sets the desired output states.

Sub-index 2 is a mask that must be set for which DOUTs are to be controlled over fieldbus.

Index Sub-Index Data Type Access PDO Mapping  
3601h 0 Unsigned38 R/O No

Number of entries.

1 Unsigned32 R/W No Digital Output Mask
2 Unsigned32 R/W RxPDO Digital Output Control

Example

3601h sub-index 2 = 0x0000000F
3601h sub-index 1 = 0x00000012

In this example, DOUT1-4 sources will be "Fieldbus" and only DOUT2.STATE will be 1. DOUT1, 3, and 4 states will be 0. DOUT5 ignores the fieldbus state since the mask is not set. The value of DOUT5.STATE will be determined by whatever DOUT5.SOURCE is set to.

 